Airport Cable  

   Airport Lighting Cables FAA L-824 Type C Unshielded 5kV

FAA L-824 Airport Lighting Cables    

Applications

These cables are used for interconnecting the transformers and the current regulator of airfield lighting systems in series circuits, suitable for fixed applications such as taxiways, runways, navigational aids, and obstruction lighting, can be installed in conduit and direct burial.

Standards

FAA L-824 Type C
ICEA S-96-659/NEWA WC71

Construction

Conductor: Stranded bare copper to ASTM B3 and ASTM B8.
Separator: Semi-conductive extruded layer or semi-conductive tape.
Insulation: XLPE.

Technical Data

Rated Voltage Uo/U (Um)

5kV

Maximum Conductor Temperature

90℃

Short Circuit Temperature

250℃

Operating Temperatures

-40℃~+90℃

Minimum Bending Radius

5×OD

Lead Free

Yes

Dimensions and Weight

Construction

No. of
Strand

Nominal Insulation
Thickness

Nominal Overall
Diameter

Nominal Weight

No.× AWG

-

mm

inches

mm

inches

kg/km

lbs/kft

1×8

7/19

2.79

0.11

9.65

0.380

132

89

1×6

7/19

2.79

0.11

10.67

0.420

186

125

1×4

7/19

2.79

0.11

11.68

0.46

268

180